| Battery Size | # of Units | Length | Width | Height | kW at 15 min. | Footprint | kW/sq. ft. |
|---|---|---|---|---|---|---|---|
| 12V Top-Terminated 540 WPC Design | 40 | 43" | 32" | 78" | 129.6 | 9.6 sq. ft. | 13.5 |
| 16V Front-Terminated 925 WPC Design | 30 | 50" | 32" | 84" | 222.0 | 11.1 sq. ft. | 20.0 |
48% Improvement in Power Density
| Battery Size | # of Units | # of Strings | Length | Width | Height | System kW 15min. | Footprint | kW/sq. ft |
|---|---|---|---|---|---|---|---|---|
| 12V Top-Terminated 540 WPC Design | 320 | 8 | 344" | 32" | 78" | 960.0 | 76.44 | 12.5 |
| 16V Front-Terminated 925 WPC Design | 120 | 4 | 200" | 32" | 84" | 888.0 | 44.44 | 20.0 |
60% Improvement in Power Density
41% Reduction in Footprint
62% Reduction in Connections
50% Reduction in Strings
| Battery Size | # of Units | Length | Width | Height | kW at 15 min. | Footprint | kW/sq. ft. |
|---|---|---|---|---|---|---|---|
| 12V Top-Terminated 540 WPC Design | 40 | 43" | 32" | 78" | 129.6 | 9.6 sq. ft. | 13.5 |
| 16V Front-Terminated 800 WPC Design | 30 | 50" | 32" | 84" | 192.0 | 11.1 sq. ft. | 17.3 |
28% Improvement in Power Density
| Battery Size | # of Units | # of Strings | Length | Width | Height | System kW 15 min. |
Footprint | kW/sq. ft |
|---|---|---|---|---|---|---|---|---|
| 12V Top-Terminated 540 WPC Design | 240 | 6 | 258" | 32" | 78" | 777.6 | 28.7 | 27.1 |
| 16V Front-Terminated 800 WPC Design | 120 | 4 | 200" | 32" | 84" | 768.0 | 22.2 | 34.6 |
28% Improvement in Power Density
23% Reduction in Footprint
50% Reduction in Connections
33% Reduction in Strings